1) All remodeling and new construction must be reviewed and approved by the University Fire Marshal. Labs must be designed for the "moderate hazard" classification according to the Kentucky Building Code and applicable referenced NFPA fire codes. For laboratories in excess of "moderate hazard" classification, an exception must be obtained from the University Fire Marshal.
2) Doors
- Doors opening onto exit corridors must swing with exit egress and must be self-closing and self-latching.
- Doors within interior partitions shall be self-latching.
3) All door hardware shall meet the requirements for the physically impaired.
4) View panel
- All doors opening onto the exit corridor and within interior partitions must be provided with view panels;
- All view panels shall be 3"x33" and shall be 1/4' wire glass in steel frames.
- All view panels shall be placed directly above the self-latching hardware.
5) Any interior partitions more than 6' in height shall be extended to the floor slab above. Any exceptions must be approved by the University Fire Marshal.
6) As a minimum, a 5# ABC (all-purpose) fire extinguisher shall be provided adjacent to each door giving access to an exit corridor. Additional units may be required for a particular/specialized hazard(s).
7) Interior and/or windowless laboratories shall be provided with emergency lighting.
8) Aisles/passageways within labs shall be a minimum of 36" of clear and unobstructed width.